Four way cassette watered fan coil unit -800CFM
Payment Terms: |
T/T,L/C |
Place of Origin: |
Zhejiang, China (Mainland) |
Product Detail
Model No.:
MFP-136KM-QK1
Production Capacity:
10000PCS PER MONTH
Delivery Date:
25-30DAYS
Certification:
CE
Cooling/Heating:
Cooling/Heating
Means of Transport:
Ocean
Packing:
Standard export packing
Type:
Fan Coil Unit
Brand Name:
MECO
Cassette:
Watered
Chilled water 4 way cassette type fan coil units
water cassette air conditioner
air volume=200CFM-1400CFM
Chilled water 4 way cassette type fan coil units
water cassette air conditioner
air volume=200CFM-1400CFM
drained by water pump height=290mm
multi air flow
E-heater is optional
Duct connection is optional
Flesh air can be intake
Compact design, suitable for strict space installation.
Centrifugal fan with backward vanes, driven by a three-speed motor, statically and dynamically balanced, low noise.
Luxury shape and ABS panel
The easily removable filter is made of filtering honeycomb polypropylene fabric and supported by a plastic frame.
The drip tray is complete with a drain pump for draining the condensate water.
remote control
BMS system can be optional
Water drained pump can be select inside the unit (standard) or outside the unit(optional and easy to do maintain)
2 pipes and 2 rows type as standard.
♦ On-board thermostat and remote thermostat
♦ Electric heater
♦ Return air box
♦ Balancing valve
♦Auto swing
PERFORMANCE OF "K" STYLE CASSETTE TYPE FAN COIL(4-WAY,2TUBE) |
model(2 tube system) | MFP-34KM-(Q)KK1 | MFP-51KM-(Q)KK1 | MFP-68KM-(Q)KK1 | MFP-80KM-(Q)KK1 | MFP-85KM-(Q)KK2 | MFP-102KM-(Q)KK2 | MFP-136KM-(Q)KK2 | MFP-170KM-(Q)KK3 | MFP-204KM-(Q)KK3 | MFP-238KM-(Q)KK3 |
model | MFP-34KM-(Q)K1 | MFP-51KM-(Q)K1 | MFP-68KM-(Q)K1 | MFP-80KM-(Q)K1 | MFP-85KM-(Q)K2 | MFP-102KM-(Q)K2 | MFP-136KM-(Q)K2 | MFP-170KM-(Q)K3 | MFP-204KM-(Q)K3 | MFP-238KM-(Q)K3 |
model of panel | MB-S****K1 | MB-S****K2 | MB-S****K3 |
power supply | 220V,50Hz,1Ph |
air volume | H | m3/h | 340 | 510 | 680 | 800 | 850 | 1020 | 1360 | 1700 | 2040 | 2380 |
M | 290 | 400 | 540 | 650 | 700 | 850 | 1110 | 1400 | 1670 | 1950 |
L | 200 | 290 | 400 | 500 | 550 | 680 | 860 | 1100 | 1300 | 1520 |
static pressure | Pa | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
cooling capacity | TH | H | W | 1800 | 2700 | 3600 | 4200 | 4500 | 5400 | 7200 | 9000 | 10800 | 12600 |
BTU/h | 6142 | 9212 | 12283 | 14330 | 15354 | 18425 | 24566 | 30708 | 36850 | 42991 |
SH | W | 1365 | 2100 | 2790 | 3200 | 3365 | 4085 | 5702 | 6780 | 8240 | 9320 |
BTU/h | 4657 | 7165 | 9519 | 10918 | 11481 | 13938 | 19455 | 23133 | 28115 | 31800 |
TH | M | W | 1555 | 2341 | 3080 | 3570 | 3811 | 4510 | 6187 | 7600 | 9221 | 10513 |
SH | W | 1092 | 1680 | 2186 | 2500 | 2604 | 3130 | 4300 | 5301 | 6490 | 7300 |
TH | L | W | 1367 | 2059 | 2700 | 3201 | 3362 | 4040 | 5515 | 6733 | 8230 | 9390 |
SH | W | 883 | 1316 | 1743 | 2055 | 2117 | 2532 | 3485 | 4314 | 5314 | 5857 |
heating capacity | H | W | 2700 | 4050 | 5400 | 6350 | 6750 | 8100 | 10800 | 13500 | 16200 | 18900 |
M | W | 2187 | 3210 | 4375 | 5108 | 5435 | 6550 | 8691 | 11000 | 13259 | 15300 |
L | W | 1896 | 2812 | 3751 | 4396 | 4673 | 5570 | 7413 | 9319 | 11312 | 12890 |
noise | H | 0Pa | dB(A) | 37 | 39 | 41 | 42 | 43 | 45 | 46 | 48 | 50 | 52 |
power input | H | 0Pa | W | 37 | 52 | 62 | 65 | 76 | 96 | 134 | 152 | 189 | 228 |
waterflow volume | | m3/h | 0.31 | 0.46 | 0.62 | 0.73 | 0.77 | 0.93 | 1.23 | 1.54 | 1.85 | 2.16 |
water pressure dropping | kPa | 11.8 | 12.9 | 22.1 | 24.3 | 18.2 | 26.8 | 28.4 | 33.2 | 35.9 | 38.4 |
dimension of water(in & out)connection pipe | in | ZG3/4" | ZG3/4" | ZG3/4" | ZG3/4" | ZG3/4" | ZG3/4" | ZG3/4" | ZG3/4" | ZG3/4" | ZG3/4" |
out | ZG3/4" | ZG3/4" | ZG3/4" | ZG3/4" | ZG3/4" | ZG3/4" | ZG3/4" | ZG3/4" | ZG3/4" | ZG3/4" |
coil | type | high efficient copper pipe to wear Hydrophilic aluminum coil |
dimension of water drain pipe | mm | ¢26 | ¢26 | ¢26 | ¢26 | ¢26 | ¢26 | ¢26 | ¢26 | ¢26 | ¢26 |
net dimension | unit | L×W×H mm | 570*570*290 | | 730*730*290 | 930*930*290 |
panel | 650*650*45 | | 850*850*45 | 1050*1050*45 |
net weight | whole | kg | 24 | 24 | 26 | 27 | 33 | 34 | 34 | 40 | 41 | 42 |
| | | | | | | | | | | | | |
Testing condition: 2-tube system Cooling Entering air temperature: Dry bulb 27ºC, Wet bulb 19.5ºC Entering/out water temperature: 7ºC/ 12℃ Heating Entering air temperature: 20ºC Entering water temperature: 60ºC, Same water flow rate as for the cooling
|
|
Related Search